X-Ray generators provide the tube
current at the required voltage for x-ray production.
In a "perfect" case this would be a constant voltage, however
transformers require alternating voltages to work so some means of
producing a constant voltage across the x-ray tube from the rising
and falling voltage produced by the high tension transformer is
required.
(Siemens)
Diagram showing typical waveforms from x-ray generator output
circuits
Ripple
The deviation of the voltage waveform across the x-ray tube from
constant voltage is named ripple
.the variation in the high-voltage expressed as the percentage of
the maximum high-voltage across the X ray tube during X-ray
production:
Ripple factor (%) = 100 x (Vmax - Vmin)/Vmax
The ripple causes corresponding but relatively higher variations in
the X-ray output. It is an unwanted phenomenon in the X-ray
production due to the lengthening of the exposure time and the
reduction in the average kV. The ripple is theoretically 100% for
the old-fashioned single phase X ray generator (in practice, it is
less, however, due to the smoothening effect of the high-voltage
cable capacitance). The three-phase X-ray generator have ripple
factors in the range of about 3–25% (3-phase 6-pulse generator:
13–25%, 3-phase 12-pulse generator: 3–10%). In the medium frequency
generator, the ripple factor decreases with increasing kVp. In this
type of generator (also named high frequency or inverter generator),
the kV is controlled by adjusting the frequency of the current prior
to high-voltage transformation. Ripple is usually in the range of
4–15%. There is practically no ripple in the constant potential X
ray generator
Constant potential x-ray generator,
An X ray generator providing a nearly flat high voltage waveform for
the X ray tube.
The term may refer to
1) any generator providing high voltage with a ripple factor less
than a certain limit, e.g. 5%, or
2)* a special generator type briefly mentioned below.
1) A voltage ripple limit of 5% would include the 3-phase 12-pulse
generator and the medium frequency generator.
2)*The so-called constant potential X-ray generator is a very
large and expensive generator that provides the highest average
X-ray energy of any X-ray generator type. It is now used only for
the most demanding applications. This generator uses a three-phase
line voltage coupled directly to the primary windings of the
high-voltage transformer, i.e. without an intermediate
autotransformer. Regulation of the kilovolt peak kVp and exposure
time is done on the secondary (high voltage) side of the transformer
by means of high voltage electron tubes (triodes or tetrodes). The
high voltage supplied to the X-ray tube has a nearly flat waveform
with a ripple less than 2%.
(http://www.amershamhealth.com/medcyclopaedia)
--------------------------------------------------------------------------------------------------------1) One pulse self rectified
In the simplest case the tube acts as a rectifier and
the - a self rectified circuit
(Stylised graph of voltage v Time)

--------------------------------------------------------------------------------------------------------2) One pulse half wave rectified
In order to prevent the anode producing electrons as it
becomes hotter and the electrons flowing backwards and striking the
filament a single rectifier can be placed in series with the x-ray
tube to ensure current flows only from filament to anode. -

(Stylised graph of voltage v Time)
Advantages and Disadvantages
Inefficient use of power no x-rays produced in negative half
cycle
Possibility of reverse conduction - low power output - unless a
rectifier is used
Minimum exposure time 0.02 S to include one whole AC cycle
However the unit can be made relatively small and cheaply for
situations requiring limited output.
--------------------------------------------------------------------------------------------------------3) Two pulse full wave rectified

(http://www.amershamhealth.com/medcyclopaedia)
A bridge rectifier circuit (see rectification) inverts
the negative half cycles and double the number of positive cycles
are produced per unit time compared with a single rectifier.
- the ripple is said to be 100%.
 
http://www.eleinmec.com
Advantages and Disadvantages
The principal disadvantages are the inefficiency of radiation
production due to the pulsating waveform no providing enough voltage
to produce x-rays for a portion of the time, and the inability to
select short exposure times.
--------------------------------------------------------------------------------------------------------4)
Constant potential x-ray generator
The constant potential generator circuit has two capacitors
across the output from the rectifiers to smooth the pulsating
waveform. To further condition the waveform, there is a triode
valve in series with each lead and these control the output
via a grid connection which has control signals fed to it from a
high resistance across the output of the triodes. Once the tube
voltage has been monitored via the high resistance potential divider
it is constantly corrected by the control unit attached to the
triode valve control grids.
The triode valves also from part of the timer switching and can
operate at microsecond intervals with good accuracy. The high
voltage supplied to the X-ray tube has a nearly flat waveform with a
ripple less than 2%.
Block Diagram of Constant potential x-ray generator circuit

Output waveform from the rectifiers and the smoothed output
across the x-ray tube

http://www.eleinmec.com
Advantages and Disadvantages
High x-ray output per mAS
Smaller range of x-ray energies
Very small exposure times possible
However these generators are very expensive and tend to be large and
have the possibility of more to go wrong.
--------------------------------------------------------------------------------------------------------5) Three phase 6 Pulse
Generator
Commercial electric power, the line voltage, is usually produced and
delivered as three phase alternating current. The period of each
single phase may be 50 or 60 Hz. The period of a 50 Hz AC has a
duration of 1/50 s, or 20 ms. The three phase X ray generator
transforms and rectifies this AC into a high-voltage direct current
(DC) with either six or twelve forward pulses per 20 ms period. As
compared to the 100% ripple factor of single-phase generators,
three-phase generators dramatically reduces voltage ripple (13–25%
for 3-phase 6-pulse, 3–10% for 3-phase 12-pulse). X-ray production
is therefore much more efficient. The so-called constant potential X
ray generator produces a voltage ripple less than 2% (hence the
name), and it produces the highest average X-ray energy of any X-ray
generator type, with exposure times less than 1 ms. This kind of
generator is, however, very bulky, with high costs and inefficient
power consumption. The preferred modern generator today, is
therefore the almost equally efficient, much smaller and less costly
medium-frequency generator (also known as high frequency and
inverter generator).
An X ray generator using a 3-phase alternating current (AC) line
source, i.e. three wires, each with a single phase AC that is one
third cycle (120°) out of phase with the other two (Fig.1). The
three-phase transformer used in this generator has three sets of
primary windings and three sets of secondary windings, i.e. in
effect three separate high-voltage interconnected transformers. The
three primary and secondary windings are connected either in a wye1
configuration or a delta2 configuration. In the
three-phase six-pulse generator, rectifiers in the high-voltage
circuit produce two pulses for each line, resulting in a total of
six pulses.
Waveforms from the various circuit in a 3 phase unit parts 
Star and delta windings

(http://www.amershamhealth.com/medcyclopaedia)
Wye or Star configuration, 1
a star-shaped configuration or interconnection of the three windings
in the primary or secondary of a transformer in a three phase X ray
generator. Delta configuration, 2
one possible configuration of the windings in the primary or
secondary side of a three-phase transformer. The windings in this
transformer can be arranged as a “D“
Combinations of these configurations
in the primary and secondary windings of a transformer will give
rise to a phase shift of 30. Using one delta and one wye
configuration as secondary windings and (usually) a delta
configuration as primary winding will therefore give twelve pulses
per period of mains AC voltage.
Advantages and Disadvantages
High x-ray output per mAS
Smaller range of x-ray energies
However these generators are expensive and tend to be large and have
the possibility of more to go wrong.
--------------------------------------------------------------------------------------------------------
Three-phase twelve-pulse
generator
In the three-phase twelve-pulse generator, a different configuration
of transformers, one of each one star and delta wound
secondaries and rectifiers resulting in a total of twelve pulses
per cycle. These generators have very low ripple factor.
--------------------------------------------------------------------------------------------------------
Falling Load Generator
--------------------------------------------------------------------------------------------------------See the Mobile Generator notes in the
Tutorials section for details of generators used in Mobile equipment
--------------------------------------------------------------------------------------------------------Medium-frequency generator,
A state of the art generator design, also named high-frequency
generator and inverter generator, which uses a high-frequency
current to produce nearly constant potential voltage to the X ray
tube with a transformer of much smaller size than found in ordinary
X-ray generators.
The incoming power supply to a medium frequency generator may be an
ordinary 50 Hz (230 V) single phase current (Fig.1). This current is
rectified and smoothed and then fed to a chopper and inverter
circuit which transforms the smooth, direct current (DC) into a
high-frequency (5 - 100 kHz) alternating current (AC). (The chopper
"chops" the continuous DC into high-frequency DC pulses and the
inverter transforms this into AC.) A transformer converts this
high-frequency low-voltage AC into high-voltage AC, which then is
rectified by half wave rectification and smoothed to provide a
nearly constant potential high voltage to the X-ray tube. The
voltage is controlled by varying the frequency of the
chopper/inverter circuit, which determines the frequency of the
current delivered to the transformer. Fast exposure switching, in
the order of 1 ms, is easily obtained with the medium frequency
generator. Outline of a medium frequency generator
(Siemens)
Waveforms from the various circuit parts

(http://www.amershamhealth.com/medcyclopaedia)
Advantages and Disadvantages
One of the great benefits of this generator design, is the reduced
weight and size. The main components of the generator may be placed
within the same enclosure as the X-ray tube, or in e.g. the C-arm of
the equipment. This generator principle was previously used only in
small mobile and/or battery-powered generators with low power
rating, but today it is applied to all modern high-voltage
generators up to the highest needed power ratings above 100 kW.
Typical Generator Diagrams (Siemens)
 Typical Fluoroscopy Unit
Block Diagram (Siemens) 
--------------------------------------------------------------------------------------------------------
Advantages and Disadvantages of different generator types
The design of a generator needs to optimise the following points,
and be matched as closely as possible to the clinical requirements
of the generator usage, a point to note is that the late 1990 saw
the pinnacle of development of film screen radiography with exposure
values required for typical examinations being much less than even
ten years earlier, thus a typical chest x-ray in 1979 before rare
earth screens may have been around 25 mAS @70Kv whilst today this
may have dropped to as little as
2mAS@90 Kv, interestingly some of
the new Digital radiography systems require more exposure than the
film screen combinations they replace.
Efficiency of conversion of electrical energy to useful x-ray energy
Maximum dose rate per mAS
Power output
Low Ripple
Cost
Size / weight
Minimum exposure time
Reliability
Advantages and Disadvantages of Constant Potential and
multiphase generators compared with a basic single phase generator.
(Stockley)
Advantages
More efficient conversion of electrical power to x-ray energy
More x-rays generated per mAS
Shorter exposure times possible
Sleeplessly variable range of exposure times
Disadvantages
More expensive to purchase
X-ray tube to cope with higher loading required
Lower image contrast
Shorter tube life
Equipment larger and heavier
Possibly more prone to failure due to greater complexity
--------------------------------------------------------------------------------------------------------Indicative Reading
Stockley, S (1986) A Manual of Radiographic Equipment.
London, Churchill Livingstone
Mobile X-Ray Generators: a review By Evans, Harris, Lawinski &
Hendra
Radiography March/April 1985 Vol. 51 No: 506 |